Toshiba Adjustable Speed Drive H3 Operation Manual page 99

Variable torque adjustable speed drive
Table of Contents

Advertisement

Preset Speed Example
The following example uses "S1" and "S2" terminals to access three preset speeds of 11.0 Hz
(close "S1"-"CC"), 55.0 Hz (close "S2"-"CC"), and 33.7 Hz (close "S1" and "S2" to "CC"). "F"-"CC"
and "ST"-"CC" must be made on the drive's terminal strip. This example assumes drive is
defaulted to factory settings prior to when the following programming is done.
Group
UTILITY PARAMETERS
UTILITY PARAMETERS
FREQUENCY SETTING PARAMETERS PRESET SPEED SELECTION
FREQUENCY SETTING PARAMETERS PRESET SPEED MODE ACTIVATION
FREQUENCY SETTING PARAMETERS PRESET SPEED #1 FREQUENCY
FREQUENCY SETTING PARAMETERS PRESET SPEED #1 OPERATING MODE
FREQUENCY SETTING PARAMETERS PRESET SPEED #2 FREQUENCY
FREQUENCY SETTING PARAMETERS PRESET SPEED #2 OPERATING MODE
FREQUENCY SETTING PARAMETERS PRESET SPEED #3 FREQUENCY
FREQUENCY SETTING PARAMETERS PRESET SPEED #3 OPERATING MODE
Trim Pot Example
This example uses the "RX" terminal to trim a reference (i.e. a 4-20 mA input) +7/-5 Hz.
Group
UTILITY PARAMETERS
UTILITY PARAMETERS
UTILITY PARAMETERS
FEEDBACK PARAMETERS
FREQUENCY SETTING PARAMETERS RX TERMINAL STANDARD OR ADJUSTABLE
FREQUENCY SETTING PARAMETERS RX REFERENCE SETTING POINT #1
FREQUENCY SETTING PARAMETERS RX REFERENCE POINT #1 FREQUENCY
FREQUENCY SETTING PARAMETERS RX REFERENCE SETTING POINT #2
FREQUENCY SETTING PARAMETERS RX REFERENCE POINT #2 FREQUENCY
Motor Operated Pot
The following programming allows a drive to emulate motor operated pot control. Momentarily
shorting "S1"-"CC" increases frequency reference. Momentarily shorting "S2"-"CC" decreases
frequency reference. Momentarily shorting "S3"-"CC" erases frequency reference. "F"-"CC" and
"ST"-"CC" must be made on the drive's terminal strip. This example assumes drive is defaulted to
factory settings prior to the following programming is done.
Group
UTILITY PARAMETERS
UTILITY PARAMETERS
UTILITY PARAMETERS
TERMINAL SELECTION PARAMETERS INPUT TERMINAL SELECTION
TERMINAL SELECTION PARAMETERS "S1" INPUT TERMINAL FUNCTION
TERMINAL SELECTION PARAMETERS "S2" INPUT TERMINAL FUNCTION
TERMINAL SELECTION PARAMETERS "S3" INPUT TERMINAL FUNCTION
FREQUENCY SETTING PARAMETERS
TOSHIBA
Parameter
BLIND FUNCTION SELECTION
FREQUENCY SETTING PARAMETERS BLIND
Parameter
BLIND FUNCTION SELECTION
FEEDBACK CONTROL PARAMETERS BLIND
FREQUENCY SETTING PARAMETERS BLIND
OVERRIDE CONTROL SELECTION
Parameter
BLIND FUNCTION SELECTION
TERMINAL SELECTION PARAMETERS BLIND
FREQUENCY SETTING PARAMETERS BLIND
FREQUENCY PRIORITY SELECTION #1
9 - 30
Value
1
1
3
0
11
0
55
0
33.7
0
Value
1
1
1
3
1
0 %
7 HZ
100 %
-5 HZ
Value
1
1
1
1
34
35
36
5

Hide quick links: