Toshiba Adjustable Speed Drive H3 Operation Manual page 60

Variable torque adjustable speed drive
Table of Contents

Advertisement

GROUP:COMMUNICATION SETTING PARAMETERS
LIQUID CRYSTAL DISPLAY
TOSLINE-F10/S20
MONITOR OUTPUT
TOSLINE-F10/S20 COMM
ERROR MODE
RS485/12-BIT BINARY
BIAS, GAIN
RS485/12-BIT BINARY
POINT #1
RS485/12-BIT BINARY
POINT #1 FREQ
RS485/12-BIT BINARY
POINT #2
RS485/12-BIT BINARY
POINT #2 FREQ
*Item 268 is available only when Item 264 Adjustment Range option 2 or 3 is selected.
**Items 271 - 274 are available only when Item 270 Adjustment Range option 1 is selected.
Cycle power after changing any parameter in GROUP:COMMUNICATION SETTING PARAMETERS.
TOSHIBA
ITEM
PARAMETER
NO.
DESCRIPTION
268*
TOSLINE-F10/TOSLINE-S20
monitor output
269
TOSLINE-F10
TOSLINE-S20
communication error mode
270
RS485/12-bit binary input: bias
and gain settings
271**
Point #1 setting signal
272**
Output Hz desired with input
entered in Item 271
273**
Point #2 setting signal
274**
Output Hz desired with input
entered in Item 273
8 - 25
(cont'd)
DISPLAY
ADJUSTMENT
RESOLUTION
RANGE
0: Off
-
1: Output frequency
2: Status
3: Output
frequency, status
4: Output current
5: Output
frequency,
output current
6: Status, output
current
7: Output
frequency,
status,
output current
8: Output voltage
9: Output
frequency,
output voltage
10:Output voltage,
status
11:Output
frequency,
output voltage,
status
12:Output voltage,
output current
13:Output voltage,
output current,
output frequency
14:Output voltage,
output current,
status
15:Output voltage,
output current,
output frequency,
status
0: Data cleared
-
1: Data retained
0: Off
-
0
1: On **
0 - 100% of
1%
Max. Out. Freq.
0 - Max. Out. Freq.
0.1/0.01 Hz
0 - 100% of
100%
Max. Out. Freq.
0 - Max. Out. Freq. 0.1/0.01 Hz
FACTORY
PAGE
SETTING
NO.
0
9-23
0
9-23
0
9-23
0
9-23
0.0
9-23
100
9-23
80.0
9-23

Hide quick links: