Toshiba Adjustable Speed Drive H3 Operation Manual page 76

Variable torque adjustable speed drive
Table of Contents

Advertisement

TOSHIBA
Item 37 JUMP FREQUENCY BAND #1 - Enter the bandwidth for JUMP FREQUENCY #1. The value
entered here will be added to and subtracted from JUMP FREQUENCY #1 to determine the upper and
lower frequencies of the deadband.
Item 38 JUMP FREQUENCY #2 - see item 36.
Item 39 JUMP FREQUENCY BAND #2 - see item 37.
Item 40 JUMP FREQUENCY #3 - see item 36.
Item 41 JUMP FREQUENCY BAND #3 - see item 37.
JUMP FREQUENCY #1
JUMP FREQUENCY BAND #1
ic
PWM CARRIER FREQUENCY
noise. Derate its current capability (110%<= 8Khz, 90%>=10Khz).
Item 43 INPUT TERMINAL SELECTION - With this parameter set to "0", the drive's input terminals, when
shorted to "CC", have the following default functions:"R" terminal gives reverse run command, "F" terminal
gives forward run command, "RES" terminal resets a fault, "ST" terminal enables drive, "S1", "S2", "S3",
and "S4" terminals give preset speed references. The user has the option of changing the function as-
signed to any of the G3's input terminals by programming a "1" into item 43 and programming the following
parameters as necessary.
Item 44, "R" INPUT TERMINAL FUNCTION - sets the function realized when the "R" terminal is shorted
to "CC". Default setting gives a reverse run command. See page 9-9 for codes for other available
functions.
Item 45, "S1" INPUT TERMINAL FUNCTION - sets the function realized when the "S1" terminal is
shorted to "CC". Default setting gives a preset speed reference. See page 9-9 for codes for other available
functions.
Item 46, "S2" INPUT TERMINAL FUNCTION - sets the function realized when the "S2" terminal is
shorted to "CC". Default setting gives a preset speed reference. See page 9-9 for codes for other available
functions.
Item 47, "S3" INPUT TERMINAL FUNCTION - sets the function realized when the "S3" terminal is
shorted to "CC". Default setting gives a preset speed reference. See page 9-9 for codes for other available
functions.
Item 48, "S4" INPUT TERMINAL FUNCTION - sets the function realized when the "S4" terminal is
shorted to "CC". Default setting gives a preset speed reference. See page 9-9 for codes for other available
functions.
Item 49, "F" INPUT TERMINAL FUNCTION - sets the function realized when the "F" terminal is shorted
to "CC". Default setting gives a forward run command. See page 9-9 for codes for other available