Item 28, ACC/DEC #1 OR #2 SELECTION - If the keypad is being used for the RUN/STOP command,
then change this parameter to choose which times and pattern are currently utilized. If the drive is getting
a run/stop command via the terminal strip (i.e. "F"-"CC" made or "R"-"CC" made), the user can remotely
choose which accel/decel is used by the drive by programming one of the input terminal's functions (see
items 44-54) to a value of "9" and then closing this terminal to "CC" when acc/dec #2 is to be used. See
item 24, ACC/DEC #1/#2 SWITCH FREQUENCY to change which acc/dec time is used based on drive's
output Hz.
Item 29, PANEL RESET SELECTION - Use this parameter to limit the type of fault that can be manually
reset from the panel:
0: Overcurrents, overloads, overvoltages, and overheat
1: Only overload faults
2: Only overload and overcurrent faults
PANEL FEEDBACK CONTROL Turns feedback on/off when stop/starting from keypad."0" allows
keypad to set setpoint. "1" turns feedback off, letting keypad act as a regular frequency referrence.
START-UP FREQUENCY
END FREQUENCY
RUN FREQUENCY
RUN FREQUENCY HYSTERESIS
FREQUENCY.
Frun + Fhys
Frun
Frun - Fhys
Item 35 JUMP FREQUENCY ENABLE - This parameters allows the programming of "Jump Frequencies",
which are bands of output frequencies the drive will not continuously output. The drive allows the user to
program up to three separate frequencies along with a bandwidth for each.
Item 36 JUMP FREQUENCY #1 - Enter the jump frequency.
TOSHIBA
START-UP FREQUENCY
HYSTERESIS CHARACTERISTIC
0
9 - 6
END FREQUENCY.
100%
RUN