PowerCube 5000
User Manual (SmartLi 100Ah)
Maintenance
Expected
Interval
Result
Every quarter
Cleanliness
Connection
Every year
Voltage
Issue 02 (2020-03-17)
Measure
Clean the battery exterior using dry cotton cloth. Exercise caution when
cleaning a battery because its voltage is high.
Check the bolt at every terminal. If any bolt is loose, tighten it.
Measure and record the busbar voltage and the positive and negative
voltages of the SmartLi. If the voltages are different, check for cable
faults and rectify them.
In the first year, collect real-time data when discharging is about to
complete at least once every six months.
From the second year, check the capacity quarterly.
Copyright © Huawei Technologies Co., Ltd.
7 Routine Maintenance
117