PARAMETER SETTINGS

5 PARAMETER SETTINGS
5
Not required
5 - 1
To operate a remote I/O network, parameters must be set up for the CPU module on
the remote master station and remote I/O modules on remote I/O stations accordingly.
Settings ranging from MELSECNET/H type selection to application function details can
be configured with parameters.
The following is a flow chart of the settings.
(1) Parameter settings for the remote master station
Setting the number of modules
Network type · · · · MNET/H (Remote master)
Network settings
(1) Starting I/O No.
(2) Network No. · · · · 1 to 239
(3) Total stations · · · ·
Remote master station only
Common parameters
(1) Transmission range of each station
(LB/LW, LX/LY setting)
Set the following items as necessary.
(2) Specify reserved station
Supplementary setting
Refresh parameter settings
Setting of valid module during other station access
Routing parameter settings
Interrupt setting parameter settings
Redundant settings for redundant system
Writing parameter to CPU module
CPU module reset
1: Refer to the Q corresponding MELSECNET/H Network System Reference
Manual (PLC to PLC network) for details.
2: Make the settings only when using the redundant system.
3: For the redundant system, write the parameter to the CPU module of the
control system.
Set the following functions
as necessary.
Required
To cable connection
MELSEC-Q
· · · ·
Section 5.1.1
· · · ·
Section 5.1.2
· · · ·
Section 5.1.3
· · · ·
Section 5.1.4
· · · ·
Section 5.1.5
· · · ·
Section 5.1.6
1
· · · ·
Section 7.7
· · · ·
Section 5.1.7
2
3
· · · ·
Section 4.6
5 - 1