APPENDICES
No.
Name
1
SW0000
(0)
Link stop/startup direction
1
content
SW0001
(1)/
SW0002
(2)/
SW0003
(3)/
SW0004
(4)
SW0008
Logical channel setting
(8)
(channel 1)
SW0009
Logical channel setting
(9)
(channel 2)
SW000A
Logical channel setting
(10)
(channel 3)
1: Used in the network test of GX Developer.
App - 15
(3) List of link special register (SW) areas
The following lists the link special register (SW) areas (SW0000 to SW01FF).
POINT
(1) Do not turn ON the area which does not exist in the list.
Doing so may cause malfunction of the programmable controller system.
(2) For how to use the link special register (SW), refer to Section 6.6.
Table 3 Link special register (SW) list
Description
Sets the station that stops/restarts data linking.
00
: Host
H
01
: All stations
H
02
: Designated station
H
80
: Host (forced stop/restart)
H
81
: All stations (forced stop /restart)
H
82
: Designated station (forced stop /restart)
H
Sets whether the designated station should execute data linking.
(When the SW0000 is 02
or 82
H
Sets the bits to 1 for stations whose data linking is
stopped/restarted.
0: Invalid data linking stop/restart instruction
1: Valid data linking stop/restart instruction
b15 b14 b13 b12
SW0001
16
15
14
13
SW0002
32
31
30
29
SW0003
48
47
46
45
SW0004
64
63
62
61
Sets the logical channel number for physical channel number 1.
(Valid only for channels on the receiving side)
0
: Logical channel number 1 (default)
1 to 64
: Other logical channel number is set.
Sets the logical channel number for physical channel number 2.
(Valid only for channels on the receiving side)
0
: Logical channel number 2 (default)
1 to 64
: Other logical channel number is set.
Sets the logical channel number for physical channel number 3.
(Valid only for channels on the receiving side)
0
: Logical channel number 3 (default)
1 to 64
: Other logical channel number is set.
.)
H
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
to
37
36
35
34
33
to
53
52
51
50
49
The numbers 1 to 64 in the above table
indicate the station numbers.
[Availability column] Optical: optical loop, Coaxial: coaxial bus
MELSEC-Q
Availability
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
: Available,
: Not available
Remote I/O
station
App - 15