Mitsubishi Electric MELSEC Q Series Reference Manual page 364

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

APPENDICES
No.
Name
2
SW0074
(116)/
SW0075
Cyclic transmission status
(117)/
of each station
W0076
(118)/
SW0077
(119)
2
SW0078
(120)/
SW0079
Parameter
(121)/
communication status of
SW007A
each station
(122)/
SW007B
(123)
2
SW007C
(124)/
SW007D
Parameter error status of
(125)/
each station
SW007E
(126)/
SW007F
(127)
2
11
SW0080
(128)/
SW0081
CPU operation status of
(129)/
each station (1)
SW0082
(130)/
SW0083
(131)
2: Valid only when SB0047 is off. When it turns on (error), the last data are retained.
11: Serious errors are the type of errors that stop the CPU operation.
Fatal errors are also the type of errors that stop the CPU operation. (Refer to Section 8.3.3.)
App - 22
Table 3 Link special register (SW) list (Continued)
Description
Stores the cyclic transmission status of each station (including
the host).
0: Executing cyclic transmission (including the station with
the maximum station number and smaller number as well
as reserved stations)
1: Cyclic transmission not executed
b15 b14 b13 b12
SW0074
16
15
14
13
SW0075
32
31
30
29
SW0076
48
47
46
45
SW0077
64
63
62
61
If a CPU module installed together with QJ71LP21S-25 is turned
OFF, detection of a data link error may take more time than
usual.
For immediate detection of a data link error, program an interlock
using the link relay (LB) in each station's send range.
For details, refer to the Q Corresponding MELSECNET/H
Network System Reference Manual (PLC to PLC network).
Stores the parameter communication status of each station.
0: Executing communication other than parameter
communication (including the stations with the maximum
station number and smaller numbers as well as reserved
stations)
1: Executing parameter communication
b15 b14 b13 b12
SW0078
16
15
14
13
SW0079
32
31
30
29
SW007A
48
47
46
45
SW007B
64
63
62
61
Stores the parameter status of each station
0: Normal parameter (including the maximum station number
and smaller numbers as well as reserved stations)
1: Abnormal parameter
b15 b14 b13 b12
SW007C
16
15
14
13
SW007D
32
31
30
29
SW007E
48
47
46
45
SW007F
64
63
62
61
Stores each station's CPU status (including the host).
Valid only for stations registered as normal in the SW0070 to
SW0073.
0: Normal (including the stations with the maximum station
number and smaller numbers as well as reserved stations)
1: Serious/fatal error
b15 b14 b13 b12
SW0080
16
15
13
14
SW0081
32
31
30
29
SW0082
48
47
46
45
SW0083
64
63
62
61
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
to
37
36
35
34
33
53
52
51
50
49
to
Numbers 1 to 64 in the above table
indicate the station numbers.
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
34
to
37
36
35
33
to
53
52
51
50
49
Numbers 1 to 64 in the above table
indicate the station numbers.
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
34
to
37
36
35
33
to
53
52
51
50
49
Numbers 1 to 64 in the above table
indicate the station numbers.
to
b4
b3
b2
b1
b0
5
3
to
4
2
1
21
20
19
18
17
to
34
to
37
36
35
33
to
53
52
51
50
49
Numbers 1 to 64 in the above table
indicate the station numbers.
MELSEC-Q
Availability
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
Remote I/O
station
App - 22

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents