Mitsubishi Electric MELSEC Q Series Reference Manual page 174

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5
PARAMETER SETTINGS
5 - 17
6)
Transient setting
Set the execution conditions for the transient transmission.
"Maximum No. of transients in 1 scan"
Set the number of transients (total for one entire network) that a single
network can execute in one link scan.
• Valid setting count : 1 to 255 times
• Default
"Maximum No. of transients in one station"
Set the number of transients that a single station can execute in one
link scan.
• Valid setting count : 1 to 10 times
• Default
2: When making the transient setting, use the following network module
and GX Developer:
• Remote master and remote I/O stations: First 5 digits of serial No.
is "07102" or later.
• GX Developer: GX Developer Version 8.29F or later
2
: 2 times
: 2 times
MELSEC-Q
5 - 17