ABB Relion 650 Series Point List Manual page 31

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 244-UUS A
Function name
FDPSPDIS
FMPSPDIS
GENPDIF
Table continues on next page
DNP, 650 series
Point list manual
Signal type
Binary inputs
Binary inputs
Binary Inputs
© Copyright 2011 ABB. All rights reserved
Signal name
ETPMMTR:ERRALM
FDPSPDIS:FWD_A
FDPSPDIS:FWD_B
FDPSPDIS:FWD_C
FDPSPDIS:FWD_G
FDPSPDIS:NDIR_A
FDPSPDIS:NDIR_B
FDPSPDIS:NDIR_C
FDPSPDIS:NDIR_G
FDPSPDIS:REV_A
FDPSPDIS:REV_B
FDPSPDIS:REV_C
FDPSPDIS:REV_G
FDPSPDIS:TRIP
FMPSPDIS:PHG_FLT
FMPSPDIS:PICKUP
FMPSPDIS:PU_A
FMPSPDIS:PU_B
FMPSPDIS:PU_C
GENPDIF:BLKH
GENPDIF:INTDIST
GENPDIF:OPENCTAL
GENPDIF:TRIP
GENPDIF:TRIPRES
GENPDIF:TRIPUNRE
Section 2
DNP3 data mappings
Description
Alarm for reactive reverse
energy exceeding limit in set
interval
Fault detected in phase
phase A- forward direction
Fault detected in phase
phase B- forward direction
Fault detected in phase
phase C- forward direction
Groundfault detected in
forward direction
Non-directional fault
detected in phase A
Non-directional fault
detected in phase B
Non-directional fault
detected in phase C
Non-directional pickup,
Phase-Ground
Fault detected in phase
phase A- reverse direction
Fault detected in phase
phase B- reverse direction
Fault detected in phase
phase C- reverse direction
Ground fault detected in
reverse direction
Trip by pilot communication
scheme logic
Ground fault detected
General pickup signal
Fault detected in phase A
Fault detected in phase B
Fault detected in phase C
Common harmonic block
signal
Indication that internal fault
has been detected
Open CT Alarm output
signal. Issued after a delay
General, common trip signal
Trip signal from restrained
differential protection
Trip signal from
unrestrained differential
protection
25