[4] [Measurement] display
Touch [Monitor/Operation] in the menu bar, and then touch [Measurement].
The measurement data of the temperature sensors, humidity sensors, and metering devices will appear.
Note: Measurement settings on the [Measurement] screen under the [Function1] menu are required to display the measurement
data on this screen. Refer to the Instruction Book (Initial Settings) for details.
Note: An AI controller (PAC-YG63MCA), a commercially available temperature sensor, and a humidity sensor are required to
measure the temperature and humidity.
Note: A commercially available pulse-output metering device is required to measure the electric, water, heat, and gas
consumptions using a built-in Pulse Input (PI) or PI controller (PAC-YG60MCA).
Note: The [Controller] setting will appear (only on the AE-200's LCD) when the [System Exp] setting on the [Unit Info.] screen is set
to [Expand]. Switch the [Controller] setting between [AE200] and [Exp1] through [Exp4] to display the data for each AE-200,
AE-50, and EW-50 individually.
Controller
Select [AE] to display
the data for AE-200, and
select [1], [2], [3], or [4] to
display the data for each
AE-50/EW-50.
Measurement item
Measurement value
Item
Measurement value
WT07992X02
The current measurement values will appear.
Note: The following icons are used to indicate the measuring devices. Icons will appear in
orange when the measurement value reaches the upper or lower alarm threshold value
that has been set on the [Measurement] screen.
Temperature sensor
Humidity sensor
Metering device
*1 When there is a communication error, the measurement value of the temperature or
humidity sensor will be "--."
*2 When there is a communication error, the measurement value of the metering device will be
the measured value immediately before the error detection.
*3 When there is a communication error between AE-200 and AE-50/EW-50, the measurement
value of the metering device will be "--."
Description
Upper/lower alarm
Normal
threshold value is
reached.
18
Communication
error/sensor error
*1
*1
*2*3