Appendix
A.1 List of important alarms and faults
Number Cause
F07840 The "Infeed operation" signal is not available, though
the enables for the drive have already been pending for
longer than the parameterized monitoring time (p0857).
Infeed not in operation.
Interconnection of the binector input for the 'ready'
signal is incorrect or missing (p0864).
Infeed is currently identifying the network.
A08526 No cyclic connection to the control is available.
44
Remedy
Put infeed into operation.
Check the interconnection of the binector input for
the "infeed operation" signal (p0864).
Extend monitoring time (p0857).
Wait for completion of the infeed network
identification.
Establish a cyclic connection and activate the control
with cyclic operation.
On PROFINET, check the parameters "Name of
station" and "IP of station" (r61000, r61001).
If a CBE20 is inserted and PROFIBUS should
communicate through process data interface 1, then
this has to be parameterized with the STARTER
commissioning tool or directly through p8839.
Getting Started, 01/2013, 6SL3097-4AG00-0BP2