Free space requirements
Frame
R8i
Definitions
Above
Front
Left
Right
Losses, cooling data and noise
ACS880-604-...
U
= 400 V
N
0500-3
0750-3
1000-3
1510-3
2260-3
3010-3
3770-3
U
= 500 V
N
0630-5
0940-5
1260-5
1880-5
2830-5
3770-5
4710-5
U
= 690 V
N
0870-7
1300-7
1730-7
2600-7
3900-7
5200-7
6500-7
Above
mm
in
200
7.9
Free space to enable cooling air flow
Free space for cabling
Free space for smooth installation
Free space for smooth installation
Noise level
dB (A)
72
72
74
74
76
76
77
72
72
74
74
76
76
77
72
72
74
74
76
76
77
Below
mm
in
mm
-
-
10
Losses
kW
3.1
4.8
6.3
9.7
14.5
19.3
24.1
3.3
5.0
6.6
10.0
15.0
20.0
25.1
4.2
6.3
8.4
12.6
18.9
25.2
31.5
Technical data 105
Front
Left / Right
in
mm
0.4
10
Cooling air flow
3
3
m
/h
ft
/min
1300
765
1300
765
2600
1530
2600
1530
3900
2295
5200
3060
6500
3825
1300
765
1300
765
2600
1530
2600
1530
3900
2295
5200
3060
6500
3825
1300
765
1300
765
2600
1530
2600
1530
3900
2295
5200
3060
6500
3825
in
0.4