60 Control unit

Default I/O diagram of the brake control unit

The diagram below shows the default I/O connections on the brake control unit, and describes
the use of the signals/connections.See also example circuit diagrams.
The wire size accepted by all screw terminals (for both stranded and solid wire) is 0.5 ...
2
2.5 mm
(24...12 AWG). The torque is 0.5 N·m (5 lbf·in).
XD2D
Drive-to-drive link
1
B
2
A
Drive-to-drive link (not in use by default)
3
BGND
4
Shield
X485
RS485 connection
5
B
6
A
Not in use (not in use by default)
7
BGND
8
Shield
XRO1...XRO3
Relay outputs
11
NC
12
COM
13
NO
21
NC
22
COM
23
NO
31
NC
32
COM
33
NO
XSTO
XSTO connector
1
OUT
2
SGND
3
IN1
4
IN2
5
IN1
6
SGND
Not in use
7
IN2
8
SGND
XDI
Digital inputs
1
DI1
Temp fault
2
DI2
Not in use by default
3
DI3
Not in use by default
4
DI4
Not in use by default
5
DI5
Not in use by default
1)
6
DI6
Reset
7
DIIL
Not in use by default
XDIO
Digital input/outputs
1
DIO1
Not in use by default
2
DIO2
Not in use by default
3
DIOGND
Digital input/output ground
4
DIOGND
Digital input/output ground
XD24
Auxiliary voltage output
5
+24VD
+24 V DC 200 mA
6
DICOM
Digital input ground
7
+24VD
+24 V DC 200 mA
8
DIOGND
Digital input/output ground
DICOM=DIOGND
Ground selection switch
XAI
Analog inputs, reference voltage output
1
+VREF
10 V DC, R
2
-VREF
-10 V DC, R
3
AGND
Ground
4
AI1+
Not in use by default.
5
AI1-
0(4)...20 mA, R
6
AI2+
Not in use by default.
7
AI2-
0(2)...10 V, R
XAO
Analog outputs
1
AO1
1)
Zero
0...20 mA, R
2
AGND
3
AO2
1)
Zero
0...20 mA, R
4
AGND
XPOW
External power input
1
+24VI
2
GND
24 V DC, 2.05 A
3
+24VI
4
GND
X12
Safety functions module connection
X13
Control panel connection
X205
Memory unit connection
1)
XRO1: Running
(energized = running)
250 V AC / 30 V DC / 2 A
XRO2: Fault (-1)
1)
(energized = no fault)
250 V AC / 30 V DC / 2 A
1)
XRO3: Running
(energized = running)
250 V AC / 30 V DC / 2 A
XSTO connector. Both circuits (power module, control unit) must be closed for
the brake unit to start. (IN1 and IN2 must be connected to OUT.)
1)
(0 = overtemperature)
(0
1 = fault reset)
4)
4)
5)
1...10 kohm
L
1...10 kohm
L
3)
= 100 ohm
in
2)
> 200 kohm
in
< 500 ohm
L
< 500 ohm
L
6)