General Notes; Static Electricity; Optical Components; Measuring The Insulation Of Brake Resistor And Resistor Cable - ABB ACS880-604 Hardware Manual

3-phase brake units as modules
Hide thumbs Also See for ACS880-604:
Table of Contents

Advertisement

General notes

Static electricity

WARNING!
Use a grounding wrist band when you handle printed circuit boards. Do not touch
the boards unnecessarily. The boards contain components sensitive to electrostatic
discharge.

Optical components

WARNING!
Obey these instructions. If you ignore them, damage to the equipment can occur.
Handle the fiber optic cables with care.
When you unplug the fiber optic cables, always hold the connector, not the cable itself.
Do not touch the ends of the fibers with bare hands as the ends are extremely sensitive
to dirt.
Do not bend the fiber optic cables too tightly. The minimum allowed bend radius is
35 mm (1.4").
Measuring the insulation of brake resistor and resistor
cable
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death, or
damage to the equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
1. Stop the drive and do the steps in section
you start the work.
2. Make sure that the resistor cable is connected to the resistor and disconnected from
the drive output terminals.
3. At the drive end, connect the R+ and R- conductors of the resistor cable together.
Measure the insulation resistance between the conductors and the PE conductor with
a measuring voltage of 1000 V DC. The insulation resistance must be higher than
1 Mohm.
ohm
1 kV DC,
> 1 Mohm
Electrical safety precautions (page 50)
R+
R-
PE
Electrical installation 51