26 Operation principle and hardware description

Type designation of the module

Type designation describes the composition of the module in short. The complete designation
code is divided in subcodes:
The first digits form the basic code. It describes the basic construction of the module.
The fields in the basic code are separated by hyphens.
The plus codes follow the basic code. Each plus code starts with an identifying letter
(common for the whole product series), followed by descriptive digits. The plus codes
are separated by plus signs.
The subcodes are described below.
CODE
DESCRIPTION
Basic codes
ACS880
Product series
104
Construction: Inverter, supply, converter or brake module.
Size
xxxxx
Refer to the ratings table in the technical data.
Voltage range
3
513...566 V DC. This is indicated in the type designation label as typical input voltage level
566 V DC.
5
513...707 V DC. This is indicated in the type designation label as typical input voltage levels
566/679/707 V DC.
7
709...976 V DC. This is indicated in the type designation label as typical input voltage levels
742/849/976 V DC (849 V DC for UL/CSA).
Option codes (plus codes)
C183
Internal heating element
C188
Direct-on-line (DOL) cooling fan
E205
Internal du/dt filtering. Included in the module delivery as standard.
G304
115 V auxiliary voltage supply
P904
Extended warranty 24/30
P909
Extended warranty 36/42