ABB ACS880-604 Hardware Manual page 107

3-phase brake units as modules
Hide thumbs Also See for ACS880-604:
Table of Contents

Advertisement

Air temperature
Relative humidity
Contamination
Chemical gases
Solid particles
Vibration
Shock
IEC 60068-2-27:2008,
EN 60068-2-27:2009
Environmental testing -
Part 2-27: Tests - Test Ea
and guidance: Shock
0 ... +45 °C
(+32 ... +113 °F), no con-
densation allowed. Output
derated in the range
+45 ... +55 °C
(+113 ... +131 °F).
Maximum 95%, no con-
densation allowed
No condensation allowed. Maximum allowed relative humidity is 60% in the presence
of corrosive gases.
IEC/EN 60721-3-3:2002:
Classification of environ-
mental conditions - Part 3-
3: Classification of groups
of environmental paramet-
ers and their severities -
Stationary use of weather
protected locations
Class 3C2
Class 3S1
No conductive dust al-
lowed.
IEC 61800-5-1
IEC 60068-2-6:2007,
EN 60068-2-6:2008 Envir-
onmental testing Part 2:
Tests -Test Fc: Vibration
(sinusoidal)
10 ... 57 Hz, max.
0.075 mm amplitude
57 ... 150 Hz 1 g
Tested in a typical cabinet
assembly according to:
Max. 1 mm (0.04 in.)
(peak value, 5 ... 13.2 Hz),
max. 0.7 g
(13.2 ... 100 Hz) sinusoidal
Not allowed
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed
IEC 60721-3-1
Class 1C2
Class 1S3 (packing must
support this, otherwise
1S2)
IEC/EN 60721-3-1:1997
With packing max.
2
2
100 m/s
(330 ft./s
) 11 ms
Technical data 107
-40 ... +70 °C
(-40 ... +158 °F)
Maximum 95%, no con-
densation allowed
IEC 60721-3-2
Class 2C2
Class 2S2
IEC/EN 60721-3-1:1997
With packing max.
2
2
100 m/s
(330 ft./s
) 11 ms

Advertisement

Table of Contents
loading

Table of Contents