Table 1 Initial Configuration Parameters for Power Supply and Distribution Devices
Device Name
Project Configuration
■Involved □Not involved
Integrated UPS & MCCB
Note: The following device parameters are not all parameters of the devices. Only the parameters that need to be set for the project are listed. Default values will be used for the other parameters so
they do not need to be set. To view other device parameters, see the user manual for the corresponding device.
If voltage/frequency settings for power distribution devices are involved, adjust the voltage and frequency settings based on the local voltage system and check whether the voltage thresholds and
frequency hysteresis meet setting requirements before first operation.
Component
Category
Basic
Output voltage level
Output frequency
Basic Param.
Battery
capacity
Quantity
UPS-1/2
Initial Configuration Parameters for an Integrated UPS
Parameter
Default Value
Language
Password
Single/Parallel
40 kVA
80 kVA
120/128 kVA
Number of cells
Power Distribution Device Name
2
Value Range
12 languages, including English, Chinese,
English
Italian, and so on
000001
Single
400 V
380 V, 400 V, 415 V
50 Hz
100 Ah
100 Ah
100 Ah
192
UPS-1/2
/
Single, Parallel
50 Hz, 60 Hz
5 Ah–3000 Ah
180–240
Remarks
Setting
English
Default value
Single
380 V
50 Hz
27 Ah
240