Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 92

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:

Advertisement

Initial Configuration Parameters of the Electric Heater DICELL XR02CX Temperature Controller for Air Inlet Windows
Category
SET
Specified value
Hy
Temperature difference
Anti-frequent–startup delay
AC
Adjustment parameters
Cy
Probe error, compressor running time
Probe error, compressor stop time
Cn
CH
Control direction (cooling cL, heating Ht)
id
Defrosting time interval
Maximum allowed defrosting time
Md
Defrosting parameters
Display the temperature during the defrosting period (rt = actual warehouse
dF
temperature; it = temperature before defrosting starts; St = specified value; dF =
abbreviation of defrosting
Item
Default Value
Value Range
–55 °C to 99 °C
N/A
2.0 ° C
0.1 ° C to 25 ° C
0–50 min
1
0–99 min
15
0–99 min
30
cL–Ht
cL
0–99 h
6
0–99 min
30
rt – it – St – dF
it
Factory Setting
Remarks
25 ° C
N/A
20 ° C
N/A
1
N/A
0
N/A
0
N/A
Ht
N/A
0
N/A
0
N/A
it
N/A