Huawei FusionModule1000A40 Initial Configuration Parameter Manual page 90

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:

Advertisement

Table 1 Initial Configuration Parameters for Power Supply and Distribution Devices
Device Name
Project Configuration
■Involved □Not involved
Integrated UPS
Note: The following device parameters are not all parameters of the devices. Only the parameters that need to be set for the project are listed. Default values will be used for the other parameters so they do
not need to be set. To view other device parameters, see the user manual for the corresponding device.
If voltage/frequency settings for power distribution devices are involved, adjust the voltage and frequency settings based on the local voltage system and check whether the voltage thresholds and frequency
hysteresis meet setting requirements before first operation.
Component
Category
Basic
Output voltage level
Output frequency
Basic Param.
Battery
capacity
UPS-1/2
Initial Configuration Parameters for an Integrated UPS
Parameter
Default Value
Language
Password
Single/Parallel
40 kVA
80 kVA
120/128 kVA
Number of cells
Quantity
Power Distribution Device Name
2
12 languages, including English, Chinese,
English
000001
Single
208 V
50 Hz
100 Ah
100 Ah
100 Ah
192
UPS-1/2
Value Range
Italian, and so on
/
Single, Parallel
208 V, 220 V, 230 V
50 Hz, 60 Hz
5 Ah–3000 Ah
96–144
Remarks
Setting
English
Default value
Single
208 V
60 Hz
40 Ah
132