120 Technical data

Derating

Surrounding air temperature derating

In the temperature range +40...50 °C (+104...122 °F), the rated output current is derated
by 1 percentage point for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor (k):
k
1.00
0.90
0.80
+40 °C
+104 °F

Altitude derating

At altitudes 1000 ... 2000 m (3281 ... 6562 ft) above sea level, the output current derating
is 1 percentage point for every added 100 m (328 ft). For example, the derating factor for
1500 m (4921 ft) is 0.95. For altitudes above 2000 m (6562 ft), contact ABB.
If surrounding air temperature is below +40 °C, the derating can be reduced by 1.5
percentage points for every 1 °C reduction in temperature. A few altitude derating curves
are shown below.
4000 m
13123 ft
3500 m
11429 ft
3000 m
9842 ft
2500 m
8202 ft
2000 m
6562 ft
1500 m
4921 ft
1000 m
3300 ft
+20 °C
+68 °F
Derating factor 1.00
Derating factor 0.95
Derating factor 0.90
T
+50 °C
+122 °F
+25 °C
+30 °C
+77 °F
+86 °F
0.80
0.85
0.90
0.95
1.00
+35 °C
+95 °F
+40 °C
+104 °F