128 Technical data
Losses, cooling data and noise
Unit type
P
lossISU
ACS880-
kW
207-...
U
= 400 V (Range 380 ... 415 V)
N
0420A-3
4.4
0580A-3
6.1
0810A-3
9.4
1130A-3
12.2
1330A-3
13.6
1580A-3
18.7
2350A-3
28.1
3110A-3
37.5
4620A-3
56.2
U
= 500 V (Range 380 ... 500 V)
N
0400A-5
4.5
0530A-5
6.0
0730A-5
8.6
1040A-5
11.9
1420A-5
17.3
2120A-5
25.9
2800A-5
34.6
4150A-5
51.9
U
= 690 V (Range 525 ... 690 V)
N
0310A-7
6.1
0370A-7
7.1
0540A-7
10.2
0720A-7
14.3
1050A-7
20.3
1570A-7
30.5
2070A-7
40.6
3080A-7
60.9
4100A-7
81.2
5130A-7
101.5
Definitions
P
Heat dissipation. Total losses of the ISU module with nominal power
lossICU
P
Heat dissipation. Total losses of the LCL filter module at nominal power
lossLCL
P
Heat dissipation. Total losses of the ISU and LCL filter modules at nominal power
lossTOTAL
Noise
Noise with direct-on-line fans running at nominal speed
P
P
lossLCL
lossTOTAL
kW
kW
2.2
6.6
3.2
9.3
3.9
13.3
5.0
17.2
5.9
19.5
7.3
26.0
11.9
40.0
14.6
52.1
21.9
78.1
2.1
6.7
2.9
8.9
3.4
12.1
4.5
16.5
6.6
23.8
9.1
35.0
13.1
47.7
19.7
71.5
2.5
8.7
3.0
10.1
4.5
14.6
4.1
18.4
7.6
27.9
9.1
39.6
15.2
55.9
22.9
83.8
30.5
111.7
38.1
139.7
Air flow
3
3
m
/h
ft
/min
2200
1295
2200
1295
2200
1295
4100
2413
4100
2413
4100
2413
6900
4061
8200
4826
12300
7240
2200
1295
2200
1295
2200
1295
4100
2413
4100
2413
6900
4061
8200
4826
12300
7240
2200
1295
2200
1295
2200
1295
4100
2413
4100
2413
6900
4061
8200
4826
12300
7240
16400
9653
20500
12066
Noise
Efficiency
dB
%
72
97.8
72
97.7
72
97.7
74
97.8
74
97.9
74
97.7
76
97.6
76
97.6
78
97.6
72
98.1
72
98.1
72
98.1
74
98.2
74
98.1
76
98.1
76
98.1
78
98.0
72
97.7
72
97.7
72
97.8
74
97.9
74
97.8
76
97.9
76
97.8
78
97.8
79
97.8
79
97.8