Site Requirements
Mounting Structure Requirements
Installation Angle Requirements
The SUN2000 can be wall-mounted or support-mounted. Requirements for the
installation angle:
Figure 4-1 Installation angle
Installation Space Requirements
Issue 01 (2020-10-15)
The SUN2000 should be installed in a well-ventilated environment to ensure
good heat dissipation.
If the SUN2000 is installed in a place exposed to direct sunlight, the power
may decrease as the temperature rises.
You are advised to install the SUN2000 in a sheltered place or install an
awning over it.
The mounting structure where the SUN2000 is installed must be fire resistant.
Do not install the SUN2000 on flammable building materials.
The SUN2000 is heavy. Ensure that the installation surface is solid enough to
bear the weight load.
In residential areas, do not install the SUN2000 on drywalls or walls made of
similar materials which have a weak sound insulation performance because
the noise generated by the SUN2000 is noticeable.
Install the SUN2000 vertically or at a maximum back tilt of 15 degrees to
facilitate heat dissipation.
Do not install the SUN2000 with a front tilt, excessive back tilt, side tilt,
horizontally, or upside down.
Reserve enough clearance around the SUN2000 to ensure sufficient space for
installation and heat dissipation.
Copyright © Huawei Technologies Co., Ltd.
4 Installation
19