Huawei SUN2000 Series User Manual page 42

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual
Number
of PV
Strings
1
3
5
7
Procedure
Step 1 Connect the DC power cable.
Use the positive and negative Staubli MC4 metal terminals and DC connectors
supplied with the SUN2000. Using incompatible positive and negative metal
terminals and DC connectors may result in serious consequences. The caused
device damage is not covered under warranty.
● You are advised to use the PV-CZM-22100 (Staubli) crimping tool and do not
use it with the positioning block. Otherwise, the metal terminals may be
damaged.
● The PV-MS (Staubli) or PV-MS-HZ (Staubli) open-end wrench is recommended.
● Cables with high rigidity, such as armored cables, are not recommended as DC
input power cables, because poor contact may be caused by the bending of the
cables.
● Before assembling DC connectors, label the cable polarities correctly to ensure
correct cable connections.
● After the positive and negative connectors snap into place, pull the DC input
cables back to ensure that they are connected securely.
Issue 01 (2020-10-15)
Terminal Selection
PV1
PV1, PV3 and PV7
PV1, PV2, PV3, PV5 and
PV7
PV1, PV2, PV3, PV4, PV5,
PV7 and PV8
CA UTION
NO TICE
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Number
Terminal Selection
of PV
Strings
2
PV1 and PV7
4
PV1, PV3, PV5 and PV7
6
PV1, PV2, PV3, PV5, PV7
and PV8
8
PV1, PV2, PV3, PV4, PV5,
PV6, PV7 and PV8