Airflow requirements
Network voltage characteristics
Network voltage ratings
Network voltage tolerance
Network frequency
Network frequency tolerance
Maximum rate of frequency variation
Maximum phase jump of network
voltage
Network voltage distortion
Minimum network fault level
Voltage notch limits
Line voltage imbalance
Insulation voltage (Ui)
Auxiliary circuit voltage
Neutral connection systems (if any)
EMC-Environment class (according to
IEC 60439-1)
Compliance with standards
General construction aspects
EMC immunity
EMC emissions
Filter characteristics
RMS output current per power unit type
Current ratings
5 A secondary rating
CTs must be installed in closed loop configuration
CTs must be cabled to master and slave units through
daisy chain principle
A minimum airflow of cooling air has to be supplied to
each cubicle:
30A - 60A: 520 m³/h
70A - 100A: 520 m³/h
120A : 710 m³/h
208 V-240 V or 380 V-415 V between phases
+/- 10 %
50 Hz or 60 Hz
+/- 5 %
20%/s
30°
Maximum 20% phase to phase
1 MVA
No voltage notches allowed
Maximum 5% of phase to phase voltage
415V
230 Vrms
IT, TT, TNC and TNS. Earth current protection type and
sensitivity must be chosen appropriately.
2
EN-61439-1 (ed. 2.0)
EN/IEC 61000-6-2, Industrial level
EN/IEC 61000-6-4
(a)
(50Hz or 60Hz network).
Unit type 1: 30 A
Unit type 2: 45 A
Unit type 3: 60 A
Unit type 4: 70 A
Unit type 5: 80 A
Unit type 6: 90 A
Unit type 7: 100 A
Unit type 8: 120 A
Manual Power Quality Filter PQFS  Technical specifications 211