ABB PQFS Installation, Operation And Maintenance Instructions page 213

Power quality filter
Table of Contents

Advertisement

Alarm contact
Filter losses
Unit rating: 30 A
Unit rating: 45 A
Unit rating: 60 A
Unit rating: 70 A
Unit rating: 80 A
Unit rating: 90 A
Unit rating: 100 A
Unit rating: 120 A
Phase to earth resistance
Noise intensity
Communication
Programming
Fuse information
Main circuit fuses
Auxiliary circuit fuses
Main options
PQ-Link software
RS-485 Modbus adapter
Easy connection box for power cables
Cable extension kit for PQF-Manager
Remark:
(a)
Under exceptional circumstances other limits may be reached before the RMS current limit (e.g.
temperature limit, peak current limit, peak voltage limit).
Can be used to monitor the filter state (e.g. filter on/off or
specific filter warnings/alarms) and the network state.
1 universal alarm contact with two complimentary outputs
(NO/NC) on PQF-Manager. Triggered by any fault.
Maximum continuous rating: 250 Vac/1.5 A
Typical values
0.7 kW
1 kW
1.3 kW
1.8 kW
2.1 kW
2.4 kW
2.7 kW
3.5 kW
1.67 MΩ/filter unit
30A - 60A: 65.3 dBA typically
70A - 100A: 68.4 dBA typically
120A : 70.9 dBA typically
Through PQF-Manager display.
Through Modbus RTU (with optional RS485 Modbus
Adapter).
Through Modbus TCP (with Ethernet).
Through dedicated optional software PQ-link (with USB-
Ethernet).
Through PQF-Manager display.
Through USB-Ethernet with dedicated optional software
(PQ-Link).
Not included
French Ferrule 10 x 38 gG/gl, 6A, 500V, Isc ~120kA
Manual Power Quality Filter PQFS  Technical specifications 213
Maximum values
≤ 1.5 kW
≤ 1.8 kW
≤ 2.1 kW
≤ 2.6 kW
≤ 2.9 kW
≤ 3.2 kW
≤ 3.5 kW
≤ 4.3 kW