22 Operation principle and hardware description

Bypass to VFD

Open QF1
Unlock the mode selection switch
Set the mode selection switch to "Unlock position"
Open QS3
Close QS1
Close QS2
Set the mode selection switch to "Working position"
Lock the mode selection switch
Close QF1.

VFD to Maintenance

Open QF1
Unlock the mode selection switch
Set the mode selection switch to "Unlock position"
Open QS2
Open QS1
Set the mode selection switch to "Maintenance position"
Lock the mode selection switch.

Bypass to Maintenance

Open QF1
Unlock the mode selection switch
Set the mode selection switch to "Unlock position"
Open QS3
Set the mode selection switch to "Maintenance position"
Lock the mode selection switch.