Maintenance to Bypass

Check all the enclosures of bypass unit are properly closed and ready for operation
Unlock the mode selection switch
Set the mode selection switch to "Local position" or "Remote position"
Lock the mode selection switch
Close KM3
Close QF1.

VFD to Bypass

Open QF1
Hint: In case need to switch between"Local position" and "Remote position", please
apply step 2 to step 4, otherwise skip to step 5.
Unlock the mode selection switch
Set the mode selection switch to "Local position" or "Remote position"
Lock the mode selection switch
Open KM2
Open KM1
Wait for at least 3 x rotor time constant (if not available, wait for longer than 5s)
Close KM3
Close QF1.

Bypass to VFD

Open QF1
Hint: In case need to switch between "Local position" and "Remote position", please
apply step 2 to step 4, otherwise skip to step 5.
Unlock the mode selection switch
Set the mode selection switch to "Local position" or "Remote position"
Lock the mode selection switch
Open KM3
Close KM1
Close KM2
Close QF1.
Operation principle and hardware description 27