Connecting

5.7 Connect PROFIBUS PA

5.7
Connect PROFIBUS PA
Requirement
Notice
Bus cable
Use only certified bus cable for PROFIBUS PA (e.g., 6XV1830-53H10).
Procedure
In order to enable the digital outputs, proceed as follows:
1. Strip the bus cable as shown in the figure below.
2. Loosen the right-hand cable clamp.
3. Pass the bus cable through the cable joint (4).
4. Secure the cable protector with the cable clamp.
5. Connect both wires to clamp 91/92 and clamp 92/94. A particular polarity is not
Figure 5-2
(1)
(2)
Notice
Explosion protection
The use of shielded conduits for the PROFIBUS PA is absolutely necessary. As a matter of
safety, all shields should be laid two-sided, and the feed source should be connected to the
potential balance of the external area.
5-8
necessary.
10
(0.4)
(1)
PROFIBUS cable, dimensions in mm (inches)
Bus cable
Cable shield
50 (2)
(2)
SITRANS DA400 with protection against explosion
Operating Instructions, 02/2006, A5E00684661-01
5 (0.2)