7.2.2

Evaluation of analog current signals

Relates to parameters
Parameter no.
P.26 to P.29
P.30 to P.33
Procedure
The analog current signal is changed by internal measurement resistance into a voltage that
is strengthened, filtered, and changed via an analog-digital exchanger into a digital signal.
This measured value passes through a low pass filter with a fixed time constant. The
measured value is then monitored for under and overflow, which is used to derive a fault
message if appropriate. The following standardization is performed depending on the setting
for the selected parameter:
P.*
0 to 20
4 to 20
20 to 0
20 to 4
The percentage value obtained can then be displayed. It is then monitored to see if it
exceeds the associated alarm "P.30/ALI*" to "P.33/ALI*". The digital signal "dol*" is then
obtained. If the state is "0", the
"1", the
SITRANS DA400 with protection against explosion
Operating Instructions, 02/2006, A5E00684661-01
Parameter name
"INP1" to "INP4"
"ALI1" to "ALI4"
0 %
0 mA
4 mA
20 mA
20 mA
symbol (alarm received).
Adjustment/display
Comment
range
0-20
Analog signal 0 to 20 mA->0 to 100%
4-20
Analog signal 4 to 20 mA->0 to 100%
20-0
Analog signal 20 to 0 mA->0 to 100%
20-4
Analog signal 20 to 4 mA->0 to 100%
-5.0% to 105.0%
Alarm for universal inputs 1 to 4
symbol (alarm not received) is displayed, if the state is
Evaluating and processing signals
7.2 Evaluation of universal inputs
100%
20 mA
20 mA
0 mA
4 mA
7-3