Product Description (ECC800e)

3.1 Structural System

The smart module houses the battery cabinet, Converged Cabinet, and network cabinet, and
employs air channels before and after cabinets.
The cabinet possesses the following features:
Table 3-1 Cabinet specifications
Item
Color
Material
Air channel
Issue 01 (2017-04-20)
The ventilation rate of the cabinet perforated door is greater than or equal to 70%.
The cabinet houses standard 19-inch wide devices.
The 42 U cabinet allows the PDU2000 to be vertically and horizontally installed in the
rear. The 24 U cabinet allows the PDU2000 to be horizontally installed in the rear.
The position of each U is marked on the rack rail.
The front and rear doors are locked and can be unlocked only with dedicated keys.
The cabinet can be installed on a base (which needs to be prepared by customers).
The 42 U cabinet can house ICT equipment with a depth not greater than 750 mm and
allows a maximum of 200 cables to be routed from the top and a maximum of 100 cables
to be routed from the bottom.
The 24 U cabinet can house ICT equipment with a depth not greater than 600 mm and
allows a maximum of 100 cables to be routed from the top and a maximum of 100 cables
to be routed from the bottom.
The 600 mm wide network cabinet allows the routing of a minimum of 200 cables.
The 800 mm wide network cabinet allows the routing of a minimum of 400 cables.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3

System Architecture

Specifications (42 U)
Black
High-intensity class A
carbon cold rolled steel plate
and zinc-coated steel plate
Front and rear air channels
3 System Architecture
Specifications (24 U)
Black
High-intensity class A
carbon cold rolled steel plate
and zinc-coated steel plate
Front and rear air channels