Huawei FusionModule500 Manual page 34

Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Figure 3-7 Electrical conceptual diagram for the 208 V dual-live wire system configured with the
10 kVA/6 kVA UPS
Table 3-8 Power distribution system technical specifications
Item
Rated power
Rated input voltage
Rated frequency
Maximum input current
External input power
distribution circuit breaker
UPS backup power
Surge protection
Issue 01 (2017-04-20)
Specifications (10 kVA
UPS)
8.1 kW
208 V
60 Hz
48 A
63 A
Battery pack (optional):
0–3 (7 Ah/240 V)
0–3 (9 Ah/240 V)
Battery:
26 Ah/12 V
40 Ah/12 V
65 Ah/12 V
100 Ah/12 V
Level D SPD (differential
mode/common mode: 5 kA)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
Specifications (6 kVA
UPS)
4.8 kW
208 V
60 Hz
31 A
50 A
Battery pack (optional):
0–3 (7 Ah/240 V)
0–3 (9 Ah/240 V)
Battery:
26 Ah/12 V
40 Ah/12 V
65 Ah/12 V
100 Ah/12 V
Level D SPD (differential
mode/common mode: 5 kA)
28