Huawei FusionModule500 Manual page 59

Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Table 3-35 BCB_IN and BCB_OUT cascading port pin definitions
Pin
1
2
3
4
DIP Switch
Table 3-36 DIP switch description
No.
1
2
3
4
Issue 01 (2017-04-20)
Definition
BCB_IN
Signal
Description
OL
Specifies
whether the
BCB
connects to
the signal
output port.
STA
Signal output
port for the
battery circuit
breaker status
DRV
Controls battery circuit
breaker trip and receives 12 V
driving signals
GND
Secondary side ground
Definition
ADDR_1
ADDR_2
ADDR_3
ADDR_4
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
BCB_OUT
Status
Signal
Description
Description
Specifies
Grounded:
whether the
BCB
connected.
cascaded
BCBs
Disconnec
connect to the
ted: BCB
signal input
not
port.
connected.
Monitors
Grounded:
whether the
The
cascaded
battery
BCBs are
circuit
connected to
breaker is
the input.
ON.
Disconnec
ted: The
battery
circuit
breaker is
OFF.
0 V: There
is no
driving
signal for
BCB
tripping.
12 V:
There is a
driving
signal for
BCB
tripping.
Description
RS485 communications
address setting
3 System Architecture
Initial
Descrip
Status
tion
Discon
Receives
nected
BCB
comman
ds sent
by the
UPS and
supports
BCB
port
Discon
cascadin
nected
g
manage
ment.
0 V
53

Advertisement