FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
B
Table B-1 Key technical specifications
Item
Number of IT cabinets
Number of cabinets
Power system
Frequency range
Maximum power of a single cabinet
Protection level
Altitude
Installation mode
Cable and pipe routing
Operating temperature
Operating humidity
Issue 01 (2017-04-20)
Technical Specifications (Dual–Live
Wire 208 V Power System)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
B Technical Specifications (Dual–Live Wire 208 V
Specifications
≤ 2 (including the Converged Cabinet and
network cabinet)
≤ 4
208 V/2 Ph/60 Hz input, 120 V/1 Ph/60 Hz
output
40–70 Hz
3.8 kW
IP20
≤ 1000 m, derated within the altitude range
of 1000 m to 4000 m
Installed on a concrete floor or raised floor
Routed in from the top and bottom
If the battery is installed in another
equipment room, temperature of the
smart module equipment room should be
in the range of 0° C to 40° C.
If the battery is installed in the same
equipment room as the smart module,
the room temperature should be in the
range of 18° C to 27° C.
5%–95% RH
Power System)
69