4

Commissioning

The physical installation of the OccuSwitch DALI system
is described in quick start guide (that comes with the
product) and the OccuSwitch DALI datasheet .
Once installed, the OccuSwitch DALI system is ready
to be used in its default mode . However, to assign the
connected luminaires to the correct groups and to set
other settings according to the design, the OccuSwitch
DALI system needs to be commissioned . The sections in
this chapter show how this is done .
The commissioning of the OccuSwitch DALI is done using
the following equipment:
• Service pushbutton on the OccuSwitch DALI
• Potentiometer on the OccuSwitch DALI
• IRT9090 extended IR (infrared) programming and
commissioning tool
• DALI master system (BMS version only)
The table below shows what functions can be done with
each commissioning tool . Each function (except switching
on/off) is described in the subsequent sections of this
chapter .
Tool
Programming function
Service button
• Set reference light level to current level
• Set reference light level by auto-calibration
Potentiometer
• Set value of delay timer
IRT9090
• Set reference light level to current level
• Check parallel link (Walk test)
• Assign luminaires to any group
• Set light level of background lighting
• Request current application mode
• Set application mode
• Set power-up state
• Set IR group address
• Reset to factory settings
• Switch luminaires on/off
• Activate 100h burn in

Hide quick links: