OSD
LRM2090 DALI commands
Hex #
Command
C2
Returns the high bits of the random address
as HH HH
C3
Return the middle bits of the random
address as MM MM
C4
Returns the lower bits of the random
address as LL LL
A1 00
All special mode processes shall be
terminated
A3 XX
Store value XX in the DTR
A5 XX
Initialize addressing commands for slaves
with address XX
A7 00
Generate a new random address
A9 00
Compare the random address with the
search address
AB 00
Withdraw from the compare process
B1 HH
Store value HH as the high bits of the search
address
B3 MM Store value MM as the middle bits of the
search address
B5 LL
Store value LL as the lower bits of the search
address
B7 XX
Program the selected slave with short
address XX
B9 XX
Check if the selected slave has short address
XX YES/NO
BB 00
The selected slave returns its short address
XX XX
BD 00
Go into physical selection mode —
Executed for all OSD slave luminaires the same
Executed