Philips OccuSwitch DALI LRM2070 User Manual page 32

Hide thumbs Also See for OccuSwitch DALI LRM2070:
Table of Contents

Advertisement

OccuSwitch DALI
User Guide
Page 32
Manual calibration with the push button and current
light level
The following tools are required for this method:
• IR remote control unit .
• Stepladder for operating the service button .
1 Change the light level to the correct light value, using
the IR remote control .
2 Press the push button on the OccuSwitch DALI for at
least 3 seconds .
The LED blinks in a cycle of "long yellow - short green"
to indicate that calibration is about to start .
3 For a more reliable calibration, get out of the sensor's
measuring area now .
After 10 seconds the OccuSwitch DALI takes the current
light sensor value as new set point .
The LED stops its visual indication and the luminaires
flash once indicating that calibration is completed .
C Caution
When the OccuSwitch DALI is calibrated manually with
the push button and using an IR control, the offset can
be different from an automated mode .
Automatic calibration with the push button and installed
light level
The following tools are required for this method:
• IR remote control unit
• Stepladder for operating the service button .
1 Press the push button on the OccuSwitch DALI for at
least 3 seconds .
The LED blinks in a cycle of "long yellow – short green"
to indicate that calibration is about to start .
2 Within 10 seconds, press the push button again .
The LED blinks in a cycle of "long red – short green" to
indicate that calibration is about to start .
3 For a more reliable calibration, get out of the sensor's
measuring area now .
After 10 seconds the OccuSwitch DALI switches the
lights OFF .
After 2 seconds the OccuSwitch DALI takes a
measurement of the Light sensor to measure the light
level when the lights are OFF .
The OccuSwitch DALI then switches the lights ON at
100% .
After 10 seconds the OccuSwitch DALI takes a
measurement of the Light sensor to measure the light
level when the lights are fully ON .
The LED stops its visual indication and the luminaires
flash once indicating that calibration is completed .

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents