ABB ARR600 User Manual page 44

Wireless i/o gateway
Hide thumbs Also See for ARR600:
Table of Contents

Advertisement

Section 9
IEC-104 application settings
38
Name
Description
Stop bits
Number of stop bits used on IEC-101 serial communication
Use HW flow
HW flow control mechanism (RTS/CTS) on IEC-101 serial
control
communication. Note: The HW handshaking is available only on
RS-232 mode.
Network
The Network settings define the general TCP/IP networking
settings
properties between the device and the IEC-104 master.
Network
Network protocol defines the network transmission layer protocol
protocol
(either TCP or UDP) used on IEC-104 network communication.
The IEC-104 standard protocol uses TCP, but for reliable slow
speed packet switched networks (for example Mobitex), the
UDP protocol can be used to minimize the packets transmitted
over network. Note: The IEC-104 standard specifies only TCP
protocol.
Network
TCP or UDP port number to listen for incoming IEC-104
protocol to
connections
listen
Network idle
Network idle timeout defines the idle timeout of the network
timeout
connection in seconds. If there is no network data received
during the specified interval, the connection is closed by the
device. This parameter is required in order to detect partially
closed connections and release the resources for new
connections especially if the
is disabled. Value "0" disables the network idle timeout
detection. The network idle timeout must be longer than IEC-104
link test interval (t3).
New
It defines the action when a new connection request arrives
connection
while a connection is already active. If the set value is "No", the
priority
new connection is rejected. If the set value is "Yes", the present
connection is terminated and the new connection is accepted. It
is recommendable to set this value to "Yes" in normal
configurations having only one IEC-104 master.
Max clients
Max clients defines the maximun number of connections
(redundancy group).
IEC-104
The IEC-104 settings define the properties of IEC-104 link layer
settings
and application layer parameters as described in the IEC
60870-5-104 standard. The IEC-104 communication is carried
out between the device and the IEC-104 master over the TCP/IP
network.
TX window
TX window size defines the maximum number of I format APDU
size (k)
packets the device may send before requiring the IEC-104
master to acknowledge them. If there are
frames sent the device stops polling IEC-101 slave for events
until acknowledgement is received. The
than the maximum sequence number defined below. The
IEC-104 standard suggests
RX window
RX window size defines the maximum number of I format APDU
size (w)
packets the device may receive before sending
acknowledgement to the IEC-104 master. The
exceed two-thirds of TX window size
w to be 8.
suggests
I frames TX
It defines the timeout in seconds the device waits for
timeout (t1)
acknowledgement from IEC-104 master after sending last I
format APDU or control frame (e.g. link test). If no
acknowledgement is received during the defined time the device
will close the network connection and the IEC-101 link. The t1
must be longer than the network round-trip-time. The IEC-104
standard suggests 15 seconds.
Table continues on next page
New connection priority parameter
k unacknowledged
k must be always less
k to be 12.
w should not
k . The IEC-104 standard
1MRS758458 F
Value range
1, 2
No, Yes
UDP, TCP
0...65000
0...65000
No, Yes
1...3
1...20
1...20
1...255
ARR600
User Manual