Section 10
Modbus application settings
46
Name
Description
Use HW
Enables CTS/RTS handshaking if set to "Yes".
handshaking
(CTS/RTS)
Gateway
mode
Gateway
If set to "Network master to serial slaves", the slaves are on the
mode
serial side.
Protocols
Serial protocol
Defines the Modbus protocol that serial devices use in serial
communication. The possible settings are Modbus RTU protocol
and Modbus ASCII protocol. ModbusRTU is recommended
because it is more efficient.
Network
Defines the TCP/IP and Modbus protocol used on network
protocol
communication. Possible protocols are Modbus TCP protocol
over TCP, Modbus RTU protocol over TCP, Modbus RTU
protocol over UDP, and Modbus ASCII protocol over UDP.
Framing
Slave
Defines the time in microseconds (millionths of a second) how
response
long the device waits for the response from a Modbus slave. If
timeout
the response is not received, the device can generate and return
a Modbus gateway exception. The reply timeout of the Modbus
master must be greater than the gateway device timeout.
Otherwise, the flow of request-reply communication is violated.
The device does not accept a new request before the reply from
the slave is received or the reply timeout is elapsed. The delays
in network communication can vary especially in wireless
networks. When the slaves are located on the network side, ping
or another method should be used to estimate the delay packets
spend on network.
Inter-frame
Defines the idle time in microseconds (millionths of a second)
timeout
that marks the end of Modbus frame in serial communication. If
the value is zero, the device uses the standard 4 character time.
The recommendation is to use a value as small as possible to
speed up communication and increase the value if problems
arise. Some PC programs can insert unexpected delays
between serial characters.
Exceptions
Generate
Defines if the device generates and returns a Modbus gateway
gateway
exception message to the master if no valid reply is not received
exceptions
from the slave. If set to "Yes", the generation of exceptions is
enabled. This functionality is useful for debugging.
Pass gateway
If set to "Yes", gateway exception replies from the slave side are
exceptions
passed to the master. If set to "No", the replies are filtered away.
Network
server settings
Table continues on next page
1MRS758458 F
Value range
No, Yes
Network master
to serial slaves
ModbusRTU,
ModbusASCII
ModbusTCP,
ModbusRTU
over TCP,
ModbusRTU
over UDP,
ModbusASCII
over TCP,
ModbusASCII
over UDP
0...90 000 000
(0...90
seconds)
0...2 000 000
(0...2 seconds)
No, Yes
No, Yes
ARR600
User Manual