1MRS758458 F
11.2.2
11.2.3
11.3
ARR600
User Manual
Digital output (IO-2)
The device has four isolated digital outputs with a shared common pin. The digital
outputs are polarity free. The digital output can be used for controlling low current
external devices. The output is a CMOS relay which is protected by a PTC type
fuse. The output is capable of handling a continuous current of 100 mA maximum
at an ambient temperature of 20°C.
Analog input (IO-2)
Table 23:
Analog input IO-2 description
Parameter
Current measuring range
Input impedance
Maximum withstanding inputs
ESD protection
Isolation
DC output
The input voltage to the power supply connector is circulated back to the I/O
connector of the device. This DC output can be used, for example, together with
digital outputs in order to simplify external circuitry and wiring.
Value
Note
4...20 mA, ±1.5 mA
Positive margin +15%
(-10...+55°C, 4...20
mA)
250 Ω
Current input
35 mA
Current input
82 V
Chip varistor protection
100 V
Section 11
I/O interface
53