Restoring factory default settings

1.
In the left pane, under Tools, click Default settings.
2.
Select a configuration profile to overwrite with the factory default settings.
3.
Click Submit.
4.
In the confirmation dialog, click OK.
5.
Restart the device.

Updating the firmware

Save a configuration profile as a backup of the current configuration before starting
the firmware update.
Check that a valid firmware package is stored on the PC before attempting to
update the firmware.
1.
In the left pane, under Tools, select Firmware Update.
The current firmware version is shown in the Firmware Update view.
2.
Click Browse to open the file selection dialog.
3.
Select the new firmware file.
4.
Click Update.
A confirmation dialog opens.
5.
Click OK to confirm firmware.
The update takes a few minutes.
6.
Once the update is finished, restart the device.

Saving configuration profiles

It is possible to save the device's configuration in a profile for use in other devices
or as a backup when updating the firmware. The configuration can be exported as
an XML file.
1.
In the left pane, under Tools, select Configuration profiles.
2.
Click Create a new profile.
3.
Select a profile to clone.
Selecting Last Boot allows saving the configuration in use when the device
was booted the previous time.
4.
Type a name for the profile.
5.
Click Submit to save the profile.
It is possible to clone, export, and import profiles in the same view.
1MRS758458 F
ARR600
User Manual