Installation and enclosure design
2.3.2
Amount of heat generated by the inverter
Installing the heat sink inside the enclosure
When the heat sink is installed inside the enclosure, the amount of heat generated by the inverter unit and converter unit is
shown in the following tables.
Converter
FR-CC2-H[]
315K
355K
400K
450K
500K
560K
630K
Inverter
FR-A842-[]
315K
355K
400K
450K
500K
NOTE
• The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
Installing the heat sink outside the enclosure
When the heat sink is protruded through a panel, the amount of heat generated by the inverter unit and converter unit is
shown in the following tables. (For the details on protruding the heat sink through a panel, refer to
Converter
FR-CC2-H[]
315K
355K
400K
450K
500K
560K
630K
Inverter
FR-A842-[]
315K
355K
400K
450K
500K
NOTE
• The amount of heat generated shown assumes that the output current is the inverter rated current, and the carrier frequency
is 2 kHz.
20
INSTALLATION AND WIRING
Amount of heat generated (W)
2350
2600
3050
3400
3800
4400
4920
Amount of heat generated (W)
SLD
LD
ND
5800
5050
4450
6690
5800
5100
7370
6480
5650
8600
7340
6500
9810
8630
7400
Heat sink section (outside of enclosure)
1640
1820
2130
2380
2660
3080
3440
Heat sink section (outside of enclosure)
SLD
LD
ND
4060
3530
3110
4680
4060
3570
5160
4530
3950
6020
5140
4550
6860
6040
5180
HD
3900
4410
4930
5650
6490
Amount of heat generated (W)
Control section (inside of enclosure)
710
780
920
1020
1140
1320
1480
Amount of heat generated (W)
Control section (inside of enclosure)
HD
SLD
2730
1740
3080
2010
3450
2210
3950
2580
4540
2950
page
24.)
LD
ND
HD
1520
1340
1170
1740
1530
1330
1950
1700
1480
2200
1950
1700
2590
2220
1950