Mitsubishi Electric A800-GF Instruction Manual page 56

Hide thumbs Also See for A800-GF:
Table of Contents

Advertisement

USB device communication
A USB (Ver. 1.1) cable connects the inverter with a personal computer.
Parameter setting and monitoring can be performed by FR Configurator 2.
Interface
Transmission speed
Wiring length
Connector
Power supply
NOTE
• For the details of FR Configurator2, refer to the Instruction Manual of FR Configurator2.
2.7.4
RS-485 terminal block
Communication operation
Conforming standard
Transmission format
Communication speed
Overall length
Connection cable
The RS-485 terminals enables communication operation from a personal computer, etc. When the PU connector is connected
with a personal, FA or other computer by a communication cable, a user program can run to monitor the inverter or read and
write parameters.
Communication can be performed with the Mitsubishi inverter protocol (computer link operation) and MODBUS RTU protocol.
(For details, refer to the FR-A800 Instruction Manual (Detailed).)
Terminating resistor switch
Initially-set to "OPEN".
Set only the terminating resistor switch of
the remotest inverter to the "100Ω" position.
P5S
SG
SDA1
(VCC)
(GND)
(TXD1+)
OPEN
VCC GND
+ TXD
100Ω
VCC GND
+ TXD
P5S
SG
SDA2
(VCC)
(GND)
(TXD2+)
NOTE
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• For wiring of the RS-485 terminals used with a plug-in option, lead the wires on the left side of the plug-in option.
Conforms to USB1.1
12 Mbps
Maximum 5 m
USB mini B connector (receptacle)
Self-powered
EIA-485 (RS-485)
Multidrop link
115200 bps maximum
500 m
Twisted pair cable (4 pairs)
SDB1
RDA1
RDB1
(TXD1-)
(RXD1+)
(RXD1-)
-
+
RXD
-
-
+
RXD
-
SDB2
RDA2
RDB2
(TXD2-)
(RXD2+)
(RXD2-)
Communication connectors and terminals