ABB ControlMaster CM15 User Manual page 37

Universal process indicator 1/8 din
Hide thumbs Also See for ControlMaster CM15:
Table of Contents

Advertisement

ControlMaster CM15
Universal process indicator
...Input/Output
Analog Outputs
Analog Output 1 (2)
Output Type
Source
Elect. Low*
Elect. High*
*Not applicable if Output Type is Digital or Source is None.
IM/CM/I–EN Rev. D
1
/
DIN
8
The analog outputs can be configured to retransmit any analog value and have a
configurable range from 0 to 24 mA.
Output 1 can also be configured to function as a digital output.
Note. Analog Output 2 is available only if Option Board 1 is fitted – see page 13.
Selects the analog or digital output (applicable only to Analog Output 1).
Selects the parameter to be assigned to the output – see Appendix A.2, page 77 for
description of sources.
The current output required when the source value is equal to the Eng Low value –
see page 33.
The current output required when the source value is equal to the Eng High value –
see page 33.