ABB ControlMaster CM15 User Manual page 75

Universal process indicator 1/8 din
Hide thumbs Also See for ControlMaster CM15:
Table of Contents

Advertisement

ControlMaster CM15
Universal process indicator
Digital Inputs
Type
Volt-free or 24 V
Single inputs configured – 250 ms
Minimum pulse
Both inputs configured as analog or digital –
duration
500 ms
Frequency input*
Frequency range
0 to 6000 Hz
1-signal
15 to 30 V
0-signal
–3 to 5 V
*For use with devices with open collector outputs
IM/CM/I–EN Rev. D
1
/
DIN
8
Outputs
Controls / retransmission outputs
Number
2 (1 standard, 1 optional)
Isolation
galvanically isolated from the rest of the circuitry,
500 V for 1 minute
Analog range
0 to 20 mA Programmable
750 Max.
Load
Accuracy
0.25 % of output or ±10µVA
Relays
Number
4 (1 standard, 3 optional)
Type
standard with changeover contacts.
optional contacts selectable as N/O or N/C
(by jumper)
Contact ratings
Relay 1:
Relays 2, 3, 4:
Relays 2, 3, 4:
Update rate
125 ms
10 Specification
5 A, 240 V
5A, 240 V (max. ambient
40 °C (104 °F)
2A, 240 V (max. ambient
55 °C (131 °F)
73