ControlMaster CM15
Universal process indicator
Icon
Number /
Possible Cause
Message
F212.018
Failure of non-volatile memory on option board 1 or
NV Error Opt Bd 1
permanent corruption of its data.
F210.019
Failure of non-volatile memory on option board 2 or
NV Error Opt Bd 2
permanent corruption of its data.
F208.020
Failure of non-volatile memory on communications board
NV Error
or permanent corruption of its data.
Comm Bd
F206.021
Failure of non-volatile memory on Software key 1 or
NV Error SW
permanent corruption of its data.
Key 1
F204.022
Failure of non-volatile memory on Software key 1 or
NV Error SW
permanent corruption of its data.
Key 2
Table 7.1 Diagnostic Messages (Continued)
62
1
/
DIN
8
Suggested Action
Check calibration of AO2, AIN 3 & AIN4 (CM50 only).
Recalibrate If necessary. Acknowledge error. If problem
persists contact local service organization.
Check calibration of AO2, AIN 3 & AIN4. Recalibrate If
necessary. Acknowledge error. If problem persists contact
local service organization.
Acknowledge error. Check communications board is
correctly identified by device. If problem persists contact
local service organization.
Acknowledge error. Check software key functionality is
enabled. If problem persists contact local service
organization.
Acknowledge error. Check software key functionality is
enabled. If problem persists contact local service
organization.
7 Advanced Level
IM/CM/I–EN Rev. D