Manual Adjustment (Depending On The Pme7); Position Of Actuator Or Speed Of Pwm Fan In Modulating Operation With Analog Signal - Siemens LME71 Series Basic Documentation

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

Note:
Display is possible only when ...
A
A
1...3 s
A
>3 s
Smart Infrastructure

15.5 Manual adjustment (depending on the PME7)

15.5.1
Position of actuator or speed of PWM fan in
modulating operation with analog signal
in operating mode or standby,
program sequence for modulating operation via analog preset output and with connected
actuator with potentiometer for position feedback to the LME7
Basic Documentation LME7...
15 Operation via internal LED
A
Press
for the relative current position of the actuator or
the relative current speed of the PWM fan.
Signal lamp blinks green.
Display shows .oP.
A
Press
(1...3 seconds) for display of the relative current
position or the current speed.
Signal lamp blinks green.
The relative value .57 of the current position is displayed.
Position of actuator 0°
0  value of potentiometer =
0% display
Position of actuator high-fire
>0°
<90° = value of
potentiometer >0  <1000 
= 100% display
Example: Value .57
A
When pressing
(>3 seconds), the point after the
number begins to blink.
When the button is released, the value is displayed for 2
minutes.
Signal lamp blinks green.
Then, the normal display appears.
Display: Value 57, point . blinks.
Actual speed
0 rpm = 0% display
Current speed corresponds
to the rated load speed =
100% display
104/116
CC1P7105en
24.07.2020

Hide quick links: