List Of Phase Display (Display Depending On Program) - Siemens LME71 Series Basic Documentation

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

Phase number
AZL2 display
Standby
OFF
Ph08
Startup
Ph21
Ph22
Ph24
Ph30
Ph36
Ph38
Ph40
Ph42
Ph44
Ph50
Ph54
Ph54
oP:P1
Operation
oP:xx
oP:P1
oP:P2
Shutdown
Ph10
Ph72
Ph74
Valve proving
Ph80
Ph81
Ph82
Ph83
Waiting phases (start prevention)
Ph01
Ph02
Ph04
Ph90
Non-alterable lockout
LOC
Smart Infrastructure

List of phase display (display depending on program)

Note
Display depending on the PME7, refer to User Documentation A7105.x.
Function
Standby, waiting for heat request
Power ON / test phase (e.g. detector test)
Safety valve ON, air pressure switch test / POC test (timeout / locking after 5 seconds),
actuator opens in low-fire position / CLOSE position
Fan motor ON and air pressure switch test / settling time
Actuator travels to the prepurge position
Prepurging
Actuator closes until ignition load / low-fire is reached, and
parameter 259.02: Actuator opens to a position > ignition load
Preignition
1st safety time / ignition transformer ON
Safety time (ignition transformer OFF), flame check
Interval: End of safety time and fuel valve V1 ON
Interval: End of safety time and load controller release
Interval: End of safety time and fuel valve V2 ON
2nd safety time
Parameter 259.01: Actuator opens to a position > low-fire
Parameter 260: Actuator closes until low-fire position is reached
Interval to release of preset load controller (analog or 3-position step input)
Operation, modulating operation
Operation first stage
Operation second stage
Actuator travels to the CLOSED position (home run)
Actuator opens until high-fire position / operation shutdown is reached
Postpurging
Test space evacuating
Test time atmospheric pressure
Test space filling
Test time gas pressure
Undervoltage / overvoltage
Safety shutdown, followed by a non-alterable lockout with interlocking
 e.g. safety loop open
Extraneous light on burner startup (timeout / locking after 30 seconds)
Pressure switch-min open
 safety shutdown / non-alterable lockout with interlocking
Lockout phase
Basic Documentation LME7...
13 Operation via AZL2
66/116
CC1P7105en
24.07.2020