Operation; Normal Display; Display In Standby Mode; Display During Startup / Shutdown - Siemens LME71 Series Basic Documentation

Burner control
Hide thumbs Also See for LME71 Series:
Table of Contents

Advertisement

Warning!
All changes to parameters and settings are only set and saved in the internal unit
memory of the LME7.
A backup must be triggered manually to save the modified settings to the PME7. Failure
to observe this information poses a risk of the safety functions being impaired.
 Chapter Operation via AZL2 / backup
 Chapter Operation via internal LED / backup
Warning!
For initial commissioning or replacement of the PME7, the function sequence and
parameter settings must be checked on completion of the restore process. Failure to
observe this information poses a risk of the safety functions being impaired.
 See chapter Operation via AZL2 / first startup, restore
 See chapter Operation via internal LED / first startup, restore
Warning!
If any parameters are changed, a backup must be made! If this is not observed, there is a
risk of loss of safety functions.
P
Smart Infrastructure
13.4

Operation

13.4.1

Normal display

Normal display is the standard display in normal operation, representing the highest
menu level. From the normal display, you can change to the info, service or parameter
level.
13.4.1.1.

Display in standby mode

V
h min s
%
13.4.1.2.

Display during startup / shutdown

Display of program phases

Basic Documentation LME7...
13 Operation via AZL2
The LME7 is in standby.
Note:
OFF flashes when manual OFF function or manual control
is active, and when controller is OFF.
The LME7 is in phase 30 (Ph30). A controller request has
been made. The bar below the symbols
The individual program phases and controlled components
are displayed in accordance with the program sequence.
and
appears.
65/116
CC1P7105en
24.07.2020