4.5 Actuators

CLOSE / ignition position / OPEN
terminal X2-09 pin 1, X2-09 pin 2, X2-
09 pin 3
Rated voltage
Rated current
Power factor
Output K2/2 X2-09 pin 7
Nominal current
Power factor
Feedback via input X2-09 pin 8 on the LME depending on the current load of the
actuator switching contact used (e.g. cam V2)!

4.6 Cross-sectional areas

The cross-sectional areas of the mains power lines (L, N, and PE) and, if required, the
safety loop (safety temperature limiter, water shortage, etc.) must be sized for rated
currents according to the selected external primary fuse. The cross-sectional areas of
the other cables must be sized in accordance with the primary fuse for the LME7 (max.
6.3 AT).
Caution!
Risk of damage to the switching contacts!
If the external primary fuse (Si) is blown due to overload or short-circuit at the
terminals, the LME7 must be replaced.
Min. cross-sectional area
Cable insulation must be suited for the respective temperature and environmental
conditions!
Basic Documentation LME7...
4 Technical data
1 mio. switching
1 mio. switching
cycles
cycles
AC 120 V 50/60 Hz
AC 230 V 50/60 Hz
0.1 A
0.1 A
Cos 0.6
Cos 0.6
AC 120 V 50/60 Hz
AC 230 V 50/60 Hz
Max. 1 A
Max. 1 A
Cos >0.4
Cos >0.4
0.75 mm²
(single- or multicore to VDE 0100)
33/116
CC1P7105enr
24.07.2020